Description
The Fire-lite BG-12LO Pull Station is a non-coded manual pull station which provides a Fire Alarm Control Panel (FACP) with a single alarm initiating input signal. Also, The pull station is a dual-action model equip with a key lock reset, an approved outdoor gasket, and an accompanying outdoor backbox. It is UL list and meets the ADA requirement of a 5-lb. maximum pull down force to activate.
The features of the pull station include Dual-Action operation, Key-Lock Reset function, Screw Terminal Wire connections, outdoor use gasket, a WBB outdoor approved 4-inch backbox, as well as a sealed switch with gold-plated switch contacts.
Besides, Install the Fire-lite BG-12LO with a listed, outdoor-approved backbox (WBB or WP-10) to meet UL requirements for outdoor use. The BG-12LO is not list for outdoor applications, without one of these backboxes . Use the four supplied 8-32 x .375″ mounting screws to attach the Pull Station to the outdoor approved backbox.
To activate the dual-action station, first push in the handle, and then pull the handle down. The handle locks into the activated position. The word ‘ACTIVATE’ appears after the handle is pull down. The pull station remains in the activated position until reset with the key lock.