Description
The Gamewell-FCI ASD-PL2F is a commercial smoke detector designed for compatible Gamewell-FCI Velociti® addressable fire alarm systems. It utilizes a smoke sensing chamber engineered to detect smoke from a wide range of combustion sources while providing dependable fire detection and reduced nuisance alarms.
The detector features programmable sensitivity, rotary decimal addressing, dual bi-color LEDs, and continuous communication with the fire alarm control panel. Its plug-in design simplifies installation, inspection, testing, and replacement. This product is intended exclusively for commercial fire alarm installations.
Product Functions
- Detects airborne smoke
- Reports alarm conditions to the fire alarm control panel
- Programmable detector sensitivity
- Continuous detector supervision
- Individual device identification
- Dual bi-color LED status indication
- Magnetic functional testing
- Automatic maintenance monitoring
Electrical & System Information
The ASD-PL2F operates on compatible Gamewell-FCI Velociti® signaling line circuits with an operating voltage range of 15–32 VDC. Detector sensitivity is programmed through the fire alarm control panel and is continuously monitored to provide maintenance alerts when cleaning is required.
The detector communicates using the Velociti grouped polling protocol, significantly improving response time compared to earlier addressable technologies. Rotary decimal switches provide local address assignment from 01–159.
Features
- Commercial smoke detector
- Velociti® communication protocol
- Programmable sensitivity
- Rotary decimal addressing
- Address range 01–159
- Dual bi-color LEDs
- Plug-in detector head
- Low-profile housing
- Magnetic functional test switch
- Noise-immune communication
- Remote LED annunciator compatibility
Mounting & Design
The ASD-PL2F installs on compatible Gamewell-FCI detector bases using a plug-in design that allows quick installation, cleaning, testing, and replacement without disturbing field wiring.
Compatible mounting boxes include 4-inch square, 3½-inch or 4-inch octagonal, and single-gang electrical boxes (depending on the selected detector base). Optional relay, isolator, and sounder bases are also available.
Protection & Applications
Suitable for:
- Office Buildings
- Schools
- Hospitals
- Hotels
- Warehouses
- Retail Facilities
- Government Buildings
- Industrial Facilities
- Commercial Properties
Compatibility
Compatible with:
- Gamewell-FCI Velociti® Fire Alarm Control Panels
- E3 Series® Fire Alarm Systems
- B501 Detector Base
- B210LP Detector Base
- B224RB Relay Base
- B224BI Isolator Base
- B200S Sounder Base
- B200SR Sounder Relay Base
- RA100Z Remote LED Indicator
Always verify compatibility with the installed fire alarm control panel, detector base, firmware version, and project requirements before installation.
Technical Specifications
Manufacturer: Gamewell-FCI
Parent Company: Honeywell
Model: ASD-PL2F
Product Type: Commercial Smoke Detector
Detection Method: Photoelectric Smoke Sensing
Communication Protocol: Velociti®
Operating Voltage: 15–32 VDC Peak
Typical Standby Current: 300 µA @ 24 VDC
Maximum Alarm Current: 6.5 mA @ 24 VDC
Address Range: 01–159
Addressing: Rotary Decimal Switches
Status Indicators: Dual Bi-Color LEDs
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Operating Humidity: 10%–93% RH Non-Condensing
Air Velocity Rating: 0–4,000 ft/min
Housing Color: White
Mounting: Compatible Detector Base Required
Application: Indoor Commercial Fire Alarm Systems
Listings: UL Listed, FM Approved, CSFM Listed, and MEA Approved (application dependent).
Applications
The Gamewell-FCI ASD-PL2F is designed for commercial fire alarm systems requiring dependable smoke detection with intelligent addressable supervision. Typical applications include office buildings, schools, hospitals, hotels, warehouses, retail facilities, industrial sites, government buildings, and other commercial occupancies utilizing compatible Gamewell-FCI Velociti® fire alarm systems.