Description
The Gamewell-FCI ASD-PTL3 is a commercial smoke and heat detector designed for compatible Gamewell-FCI addressable fire alarm systems. It combines a smoke sensing chamber with a 135°F (57°C) fixed-temperature thermal sensor, providing dependable fire detection in a single low-profile detector.
As part of the Velociti® Series 3 product family, the detector features programmable smoke sensitivity, rotary decimal addressing, dual LEDs with 360-degree visibility, and a built-in magnetic test switch for simplified installation and maintenance. This product is intended exclusively for commercial fire alarm installations.
Product Functions
- Detects airborne smoke
- Provides 135°F (57°C) fixed-temperature heat detection
- Reports smoke and heat alarm conditions to the fire alarm control panel
- Programmable smoke sensitivity
- Continuous detector supervision
- Individual device identification
- Dual LED status indication
- Built-in magnetic functional testing
Electrical & System Information
The ASD-PTL3 operates on compatible Gamewell-FCI Velociti® Signaling Line Circuits (SLC) and communicates continuously with the fire alarm control panel. Rotary decimal switches provide local device addressing from 01–159, while the detector occupies a single SLC address.
The detector combines a smoke sensing chamber with dual electronic thermistors for fixed-temperature thermal detection. Smoke sensitivity is programmable through the compatible fire alarm control panel to suit a variety of commercial environments.
Features
- Commercial smoke and heat detector
- Smoke sensing chamber
- 135°F (57°C) fixed-temperature thermal sensor
- Velociti® communication
- Rotary decimal addressing
- Dual LEDs with 360° visibility
- Built-in magnetic functional test switch
- Programmable smoke sensitivity
- Low standby current
- Plug-in detector head
- Low-profile housing
- Compatible with relay, isolator, and sounder bases
Mounting & Design
The ASD-PTL3 installs on compatible Gamewell-FCI intelligent detector bases using a plug-in design that allows installation, inspection, cleaning, testing, and replacement without disturbing field wiring.
Compatible bases include the B501, B300-6, B224RB, B224BI, B200S, B200SR, B200S-LF, and B200SR-LF, providing installation flexibility for a wide range of commercial fire alarm applications.
Protection & Applications
Suitable for:
- Office Buildings
- Schools
- Hospitals
- Hotels
- Retail Facilities
- Warehouses
- Healthcare Facilities
- Educational Campuses
- Commercial Properties
Compatibility
Compatible with:
- Gamewell-FCI Addressable Fire Alarm Control Panels
- E3 Series® Fire Alarm Systems
- S3 Series Fire Alarm Systems
- GWF-7075 Fire Alarm Control Panel
- Velociti® Signaling Line Circuits
- B501 Detector Base
- B300-6 Detector Base
- B224RB Relay Base
- B224BI Isolator Base
- B200S Intelligent Sounder Base
- B200SR Sounder Base
- B200S-LF Low Frequency Sounder Base
- B200SR-LF Low Frequency Sounder Base
Always verify compatibility with the installed fire alarm control panel, detector base, firmware version, communication protocol, and project requirements before installation.
Technical Specifications
Manufacturer: Gamewell-FCI
Parent Company: Honeywell
Model: ASD-PTL3
Series: Velociti® Series 3
Product Type: Addressable Smoke and Heat Detector
Detection Method: Smoke Sensing Chamber with Fixed-Temperature Thermal Sensor
Heat Rating: 135°F (57°C)
Communication Protocol: Velociti®
Operating Voltage: 15–32 VDC
Typical Operating Current: 200 µA @ 24 VDC
Maximum Alarm Current: 2 mA @ 24 VDC
Maximum Current: 4.5 mA @ 24 VDC
Addressing: Rotary Decimal Switches
Address Range: 01–159
Smoke Sensitivity: Programmable Through Compatible Fire Alarm Control Panel
Status Indicators: Dual LEDs (360° Visibility)
Built-In Test: Magnetic Functional Test Switch
Operating Temperature: 32°F to 122°F (0°C to 50°C)
Operating Humidity: 10%–93% RH Non-Condensing
Air Velocity: 0–4,000 ft/min
Height: 2.0 in. (51 mm)
Diameter: 4.1 in. (104 mm) on B501 Base; 6.2 in. (156 mm) on B300-6 Base
Weight: 3.4 oz. (95 g)
Housing Color: White
Mounting: Compatible Intelligent Detector Base Required
Application: Indoor Commercial Fire Alarm Systems
Listings: UL Listed for commercial fire alarm applications. Verify product labeling and project requirements before installation.
Applications
The Gamewell-FCI ASD-PTL3 is designed for commercial fire alarm systems requiring combined smoke and fixed-temperature heat detection in a single addressable device. Typical applications include office buildings, schools, hospitals, hotels, retail facilities, warehouses, healthcare facilities, educational campuses, and other commercial occupancies utilizing compatible Gamewell-FCI Velociti® fire alarm systems.