Description
The Siemens ILI-1B comes designed specifically for use with Fire Safety AD-3I air duct detector housing, and, like the ILI1A, contains a specially designed internal chamber cover. The Siemens ILI-1B must b e used with the AD-3I air duct detector housing in air duct applications with air velocities of 500-4000 ft./min. If a relay i s desired, use a DA-X3SR module with the AD-3I housing.
The ILI Series intelligent ionization detectors ar e compatible with Fire Safety SensorLINK FPI-32 or DPU field programmer/tester. The FPI-32 is a compact, portable, menu-driven accessory that makes programming and testing detectors faster, easier, and more reliable than other methods. The FPI-32 eliminates the need for cumbersome, unreliable mechanical programming methods and reduces installation and service costs by electronically programming addresses and functionally testing the ILI’s performance b efore the detector i s installed.
The ILI Series ionization detectors are compatible with Fire Safety IXL, MXL, and XL3 control panels. All ILI Series detectors come from Underwriters Laboratories Listed.
Features/ Specifications
Current Requirements: Normal – 1.2mA Typical Alarm – 1.5mA Typical
Voltage Range: *16VDC – 30VDC Peak Pulsed Voltage
Operating Temperature: +32o F (0o C) to +100o F (38o C) per UL 268/268A
Humidity: 0-93% Relative Humidity Non-Condensating
Addressable ionization detector air duct use only(with AD-3I)