Description
The Notifier NC-100R is a commercial addressable relay module designed for compatible Notifier FireWarden Series fire alarm control panels. It provides two isolated Form-C dry-contact outputs that can be programmed to control a variety of auxiliary devices, including door holders, HVAC equipment, dampers, fans, and other building control functions.
Powered directly from the Signaling Line Circuit (SLC), the module features rotary decimal addressing, integral LED status indication, and high EMI/RFI immunity for dependable operation in commercial fire alarm systems. This product is intended exclusively for commercial fire alarm installations.
Product Functions
- Controls auxiliary equipment through programmable relay outputs
- Provides two isolated Form-C dry contacts (DPDT operation)
- Supports door holder release
- Controls HVAC shutdown equipment
- Activates smoke dampers and exhaust fans
- Resets compatible four-wire smoke detector power
- Continuous SLC communication and supervision
- Individual address identification
Electrical & System Information
The NC-100R operates directly from a compatible 15–32 VDC Signaling Line Circuit (SLC) and requires no external operating power for module electronics or relay operation. Two rotary decimal switches allow simple field addressing before or after installation.
An integral green LED flashes during normal communication with the control panel and remains steadily illuminated when the relay is activated. The module occupies one address on the SLC and automatically reports its device type to the control panel.
Features
- Commercial addressable relay module
- Two isolated Form-C relay contacts
- DPDT relay operation
- Powered directly from the SLC
- Rotary decimal addressing
- Integral green status LED
- Automatic device identification
- High EMI/RFI immunity
- SEMS screw terminals with clamping plates
- Plug-in field wiring
- Compact mounting design
Mounting & Design
The NC-100R mounts to a standard 4-inch square electrical box with a minimum depth of 2.125 inches. An optional SMB500 surface-mount backbox is available for surface installations.
Its off-white heat-resistant enclosure, clamping plate terminals, and front-access rotary address switches simplify installation and servicing while providing dependable long-term operation.
Protection & Applications
Suitable for:
- Door Holders
- HVAC Shutdown
- Smoke Dampers
- Exhaust Fans
- Fire Smoke Control Systems
- Four-Wire Detector Power Reset
- Building Automation Interfaces
- Commercial Fire Alarm Systems
Compatibility
Compatible with:
- Notifier FireWarden-100-2 Fire Alarm Control Panels
- Notifier FireWarden-50 Fire Alarm Control Panels
- Compatible FireWarden Series Signaling Line Circuits
- SMB500 Surface-Mount Back Box
- Auxiliary Equipment with Dry-Contact Inputs
Always verify compatibility with the installed fire alarm control panel, SLC protocol, firmware version, and controlled equipment before installation.
Technical Specifications
Manufacturer: Notifier
Parent Company: Honeywell
Model: NC-100R
Product Type: Addressable Relay Module
Relay Outputs: Two Isolated Form-C Dry Contacts (DPDT)
Operating Voltage: 15–32 VDC
Power Source: Signaling Line Circuit (SLC)
Typical Standby Current: 230 µA (Direct Poll)
Typical Standby Current: 255 µA (Group Poll with LED Flashing)
Maximum Operating Current: 6.5 mA (LED Active)
Addressing: Rotary Decimal Switches
Address Range: 01–99 (FireWarden-100-2); 01–50 (FireWarden-50)
Status Indicator: Integral Green LED
Contact Rating: 3.0 A @ 30 VDC Resistive (Non-Coded)
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Operating Humidity: 10%–93% RH Non-Condensing
Dimensions: 4.5 × 4.0 × 1.25 in. (114.3 × 101.6 × 31.8 mm)
Mounting: Standard 4-Inch Square Electrical Box
Application: Indoor Commercial Fire Alarm Systems
Listings: UL Listed, ULC Listed, FM Approved, CSFM Listed, and MEA Approved (application dependent).
Applications
The Notifier NC-100R is designed for commercial fire alarm systems requiring addressable relay control of auxiliary building equipment. Typical applications include HVAC shutdown, smoke control systems, door holder release, damper control, fan activation, four-wire smoke detector power reset, and other programmable relay functions in offices, schools, hospitals, warehouses, industrial facilities, and other commercial occupancies.





Reviews